- 1 channel
- Low cost and easy to install
- DIN rail mounting
- 3 built-in discrete relays
- For any transmitters/detectors
- Continuous self-checkin
Spectification :
Casing
|
Size (W x H x D):
|
185 x 157 67 cm
|
Material:
|
ABS
|
Mounting:
|
By Rail DIN supplied
|
Cable entries:
|
3 cable-glands M20 (outer diameter 5.5 to 12 mm)
1 cable-glands M16 (outer diameter 4 to 8 mm)
|
Protection:
|
IP31
|
Power supply
|
Voltage:
|
230 Vac or 115 Vac and 21 Vdc to 30 Vdc (nominal 24 Vdc)
|
Consumption:
|
20 VA
|
Operating temperature:
|
-10 to + 45°C
|
Cabling
|
Sensors:
|
• 1 flammable gas detector OLC10 or 2 detectors OLC10 TWIN for detection of methane, butane, propane in boiler rooms and LPG, Natural Gas for Vehicles or H2 in car parks
• 1 flammable gas transmitter OLCT10 for detection of methane, butane, propane in boiler rooms and LPG, Natural Gas for Vehicles or H2 in car parks
• 1 to 5 similar detectors type OLCT10 for detection of CO, NO, NO2 in car parks for example
|
Maximum cable length:
|
• OLC10 (flammable only): 3-wire, shielded, core size 1 to 1.5 mm2, 300 m max
• OLC10 TWIN (flammable only): 4-wire, shielded, core size 1 to 1.5 mm2, 300 m max
• OLCT10 (flammable): 3-wire, shielded, core size 1 to 1.5 mm2, 1 Km max
• OLCT10 (toxic): 2-wire, shielded, core size 0.75 to 1.5 mm2, 4 Km max
|
Display
|
Type:
|
Liquid Crystal Display, 4 digits and extra friendly symbols
|
Visual indications:
|
4 DELs. Green: power on, Red: alarms triggered, Orange: failure
|
Gas and unit:
|
Selectable in a programmed list
|
Keyboard:
|
3 keys for access to main menu, test or acknowledgement
1 : Enter / Menu, 2 : - / test indicator, 3 : + / acknowledgement
|
Alarms & relays:
|
• 2 programmable and independent levels, falling or increasing alarms, latching or unlatching modes, local or remote acknowledgment
• 2 alarm relays normally energized, selectable normally open or normally closed (de-energized on request at the factory)
• 1 fault relay, normally energized
• Relay ratings : 2A at 250 Volts AC or 30 Volts DC
|
Approvals
|
ATEX 94/9/CE Directive
|
category 3G (flammable gas detection metrology EN 61779-1 and EN 61779-4)
|
Low Voltage Directive:
|
EN 61010
|
Electromagnetic compatibility (EEC directive):
|
EN 50270
|
|
|
|
|
|
|
HỖ TRỢ TRỰC TUYẾN |