Model
|
MX 43 gas detection control panel
|
Dimensions (wall-mounted version):
|
370 x 299 x 109 mm (14.6 x 11.8 x 4.3 inches)
|
Dimensions (rack):
|
19", 4U ; 482.8 x 177 x 192.5 mm (19.1 x 7 x 7.6 inches)
|
Ingress protection:
|
IP55 (wall-mounted), IP31 (rack)
|
Cable entries (wall-mounted version):
|
12 M16 cable glands, 4 to 8 mm2 (8 to 11 AWG) outer diameter cable
6 M20 cable glands, 6 to 12 mm2 (7 to 9 AWG) outer diameter cable
|
Display:
|
LCD back-lit display + smart keys
Display in video inverse in case of fault
Customizable by user (display 1 to 16 channels simultaneously, fixed or scrolling, on events...)
Bar graph with alarm threshold
|
Visual indicators:
|
7 LEDs per line
1 LED fault indicator
1 LED fault indicator
|
Buttons:
|
5 smart keys
1 audible alarm accept/reset button
|
Operating use
|
Operating temperature:
|
-20°C to +50°C
|
Storage temperature:
|
-20°C to +50°C
|
Humidity:
|
5 to 95% RH
|
Power:
|
100-240 Vac 50-60 Hz or 21-28 Vdc, 112 W max
|
Battery:
|
Embedded back up power supply in option (0.6 Ah)
|
Consumption:
|
500 mA min (without module)
|
Measurement lines
|
Digital lines:
|
8 maximum
RS-485 communication, proprietary protocol, 9600 Baud
2 twisted shielded-pair cable
|
Analog channels:
|
8 maximum
0-23 mA analog signal input (4 to 20 mA reserved for measurement) 120 Ohm load resistance
2 or 3-core shielded cable
|
Voltage (typical):
|
21 to 28Vdc
|
Maximum current output per line:
|
500 mA
|
Maximum current output in total:
|
2.4 A permanent (3.2 A intermittently)
|
Alarms
|
Per channel:
|
5 alarm levels (A1, A2, A3, Overscale, Underscale) + Fault
Non-ambiguity reading option for combustible gases monitoring
|
Programmable thresholds:
|
On instantenous ou averaged values, rising or falling alarms, manual or automatic acknowledgement
|
On-board relays:
|
5 fully programmable alarm relays
1 fault relay (non-configurable)
Dry contact relay
DPCO relays with contact rating of 250 Vca 2 A (inductive)
|
Digital outputs:
|
RS-485 Modbus RTU serial link
|
Approvals
|
EMC:
|
According to EN50270
|
ATEX:
|
EN50271 and metrological performances according to EN60079-29-1
|
Low Voltage Directive:
|
According to EN61010
|
CSA:
|
Pending
|